Thanks for the info Robert but I think I found the problem. I found that I have a bad limit switch; it stays open even with the unit off. I ordered one from this site, so we shall see when it comes in. Hopefully that it, if not you will see me on here again.
Thanks
Corey
Search found 4 matches
- Mon Jan 11, 2010 9:09 pm
- Forum: Nordyne Service & Repair
- Topic: Nordyne E2EB-012HA
- Replies: 7
- Views: 3094
- Sat Jan 09, 2010 7:38 pm
- Forum: Nordyne Service & Repair
- Topic: Nordyne E2EB-012HA
- Replies: 7
- Views: 3094
Re: Nordyne E2EB-012HA
I going to get a clamp ammeter and a thermometer tomorrow. What readings should I be looking for(if working right)?
- Sat Jan 09, 2010 6:52 pm
- Forum: Nordyne Service & Repair
- Topic: Nordyne E2EB-012HA
- Replies: 7
- Views: 3094
Re: Nordyne E2EB-012HA
Hi thanks for responding. I don't have a clamp amp meter just a regular meter that only goes to 10 amps. The ducts are all in the ceiling there is no way to get to them. I redid my ohm check I unwired the two elements they both read 9.5 ohms. I get 240v across the elements when on and 120 to ground ...
- Sat Jan 09, 2010 11:58 am
- Forum: Nordyne Service & Repair
- Topic: Nordyne E2EB-012HA
- Replies: 7
- Views: 3094
Nordyne E2EB-012HA
The unit is not heating like it should. Its like it not getting hot enough. The unit will come on and heat up but it seems it cant keep up and sometimes it will get colder in the house wile its running. I'm a electronics tech so I have checked and I have 240 to the two elements. The elements 11.6kw ...