colman central electric furnace
hi my heater will not come on at all i had a tec check it out and told me I'm not getting power to my thermostat serial#117960841/model#3120B750
Test across the LOAD/SECONDARY side of transformer for 24-28vac output.
IF you do not have it, test across LINE/PRIMARY side for 240vac input.
Thanks,
Robert
IF you do not have it, test across LINE/PRIMARY side for 240vac input.
Thanks,
Robert
Some people are Humbly Grateful, while some are Grumbly Hateful.................... Which one are you ?
hi Robert my transformer don't have 24-28vac it showed 0000000000 but the primary side has 240Robert wrote:Test across the LOAD/SECONDARY side of transformer for 24-28vac output.
IF you do not have it, test across LINE/PRIMARY side for 240vac input.
Thanks,
Robert
-
- Similar Topics
- Replies
- Views
- Last post
-
-
Colman evcon presidental 7980B856 furnace will not stay on
by ezridersid » Sat Dec 21, 2019 8:52 pm » in Mobile Home Repair - 1 Replies
- 17306 Views
-
Last post by ezridersid
Sat Dec 21, 2019 9:04 pm
-
-
- 3 Replies
- 37371 Views
-
Last post by David DeBord
Sun Oct 22, 2017 8:16 am
-
-
Electric water heater, standard VS. MH specific
by ferret13sj » Thu Aug 26, 2021 3:41 am » in Mobile Home Repair - 4 Replies
- 49362 Views
-
Last post by Sulteric
Sun Sep 05, 2021 9:39 pm
-
-
-
DGAT Series furnace air-conditioning issue
by minnie1967 » Thu Jul 13, 2017 9:48 am » in Coleman Service & Repair - 0 Replies
- 61916 Views
-
Last post by minnie1967
Thu Jul 13, 2017 9:48 am
-
-
-
Acceptable HEAT RISE number for this 20-yr. old furnace.
by justplumducky » Tue Aug 29, 2017 5:33 pm » in Nordyne Service & Repair - 0 Replies
- 44401 Views
-
Last post by justplumducky
Tue Aug 29, 2017 5:33 pm
-